Download Low Volt Distribution Brochure

LOW VOLTAGE DISTRIBUTION AND MOTOR CONTROL PANELS

Sivacon S8 Low Voltage Panels

Sivacon S8 and 8PT Low Voltage Type Tested Distribution Boards
Sivacons are type tested low voltage distribution boards. The Sivacon S8 and 8PT distribution boards set new standards as power distribution boards and motor control centres for industrial or commercial infrastructure. The power distribution board system allows up to 7000A for the simple and dependable distribution of power and ensures maximum personal and plant safety.

The system is based on a modular design technology that can be optimally adapted to every requirement when designing a complete low voltage solution. This allows the Sivacon range to offer a wide variety of possible uses and applications in a cost efficient manner.

• Safety at the highest level for both that of human engagement, industry and commercial plant with verifications tests that are in accordance with IEC61439-2.
• High level of flexibility in design to meet low voltage solution requirements.
• Application of a variety of switchgear, from the following leading suppliers: Eaton, Legrand, CBI, Schneider and Siemens to meet client’s specifications
subject to type tested with the variation certification.
• Our team of technical experts are available to assist in design and development of low voltage solutions.
• In addition, the ability to offer on-site installation and commissioning through a preferred installer.

Circuit Breaker SystemUniversal Installation SystemFixed-Mounted System3NJ4 In-Line SystemReactive Power Compensation3NJ6 In-Line System
Installation SystemFixed-mounted withdrawableFixed-mounted with compartment doors Plug-inFixed-mounted with front coversFixed-mountedFixed-mountedPlug-in
FunctionsSupply feeder couplingCable feedersCable feedersCable feedersCentral compensation of reactive powerCable feeders
Rated CurrentUp to 6300AUp to 630AUp to 630AUp to 630AUn-choked up to 600 kvar choked up to 500 kvarUp to 630A
Connection PositionFront and rearFront and rearFrontFrontFrontFront
Cubicle Width (mm)400/600/800/
1000/1400
600*/1000/12001000/1200600/8008001000/1200
Internal SeparationForm 1, 2b, 3a, 4bForm 2b, 3b, 4a, 4bForm 1, 2b, 4a, 4bForm 1, 2bForm 1, 2bForm 3b, 4b
Busbar PositionRear/topRear/topRear/topRearRear/top/withoutRear/top

Optional Design Modules for LV Solutions

Circuit Breaker System
Description
• Installation systems:
- fixed-mounted design
- withdrawable design
• Functions: incoming feeder, outgoing feeder, coupler
• Rated current (In): up to 6300A
• Connection position: front and rear
• Section width: 400/600/800/1000/1400mm
• Internal separation: form 1, 2b, 3a, 4b
• Busbar position: rear/top
Universal Installation System
Description
• Installation systems:
- fixed-mounted design with compartment doors
- plug-in 3NJ6 in-line design
- retractable interchangeable unit design, removable unit design
• Functions: cable feeders, motor feeders
• Rated current (In): up to 630A/up to 250kW
• Connection position: front and rear
• Section width: 600*/1000/1200mm
*not with 3NJ6
• Internal separation: form 2b, 3b, 4a, 4b
• Busbar position: rear/top
3NJ6 In - Line System
Description
• Installation systems: plug-in 3NJ6 in-line design
• Functions: cable feeders
• Rated current (In): up to 630A
• Connection position: front
• Section width: 1000/1200mm
• Internal separation: form 3b, 4b
• Busbar position: rear/top
Fixed - Mounted System
Description
• Installation systems: fixed-mounted design with front covers
• Functions: cable feeders
• Rated current (In): up to 630A
• Connection position: front
• Section width: 1000/1200mm
• Internal separation: form 1, 2b, 4a, 4b
• Busbar position: rear/top
3NJ4 In - Line System
Description
• Installation systems: fixed-mounted design
• Functions: cable feeders
• Rated current (In): up to 630A
• Connection position: front
• Section width: 600/800mm
• Internal separation: form 1, 2b
• Busbar position: rear
Reactive Power Compensation
Description
• Installation systems: fixed-mounted design
• Functions: central compensation of reactive power
• Reactive power of battery:
- non-choked up to 600kvar
- choked up to 500kvar
• Connection position: front
• Section width: 800mm
• Internal separation: form 1, 2b
• Busbar position: rear/top/without