LS RESIN CORE TRANSFORMERS

Resin Core Transformers (Oil Free)
Features
• Environmentally safe:
LS Cast Resin Transformers will not emit oil or toxic gases into the atmosphere. Therefore, they do not pollute the environment and are strongly
recommended as a replacement for askarel (PCB)- filled transformers.
• Low maintenance:
Maintenance is almost completely eliminated. No checking of liquid level and no dielectric test for moisture absorption is required. Due to the smooth coil surface, heavy dirt and dust build up are eliminated. The recommended routine maintenance is an occasional visual inspection.
• High overload capability:
Based on the high thermal time constant factor of the windings, LS Cast Resin Transformers can be overloaded for a short duration. Considerably higher than traditional oil transformers. It has
a greater capability to withstand sudden high overloads such as might be encountered in heavy traction applications.
• Moisture proof
• High impulse strength
• No partial discharge
• Fire resistant
• Low noise
• Standard: IEC 60076-11 (2004)
Information Optional Accessories
• F Class, 100K Temperature Rise, 50Hz
• 12kV Class, 75BIL
• Forced cooling fans
• PT100 probes and controllers
Rated Power Impedance Voltage No Load Loss Load Loss Efficiency Physical Attributes Product Code
100%
Load
75%
Load
50%
Load
Width Depth Height Total Mass
(kVA) (%) (W) (W) (%) (mm) (mm) (mm) (kg)
400 4.0 1150 4900 98.5 98.7 98.8 1220 800 1430 1300 N1523
630 6.0 1500 7300 98.6 98.8 98.9 1400 900 1570 1750 N1524
1000 6.0 2000 10,000 98.8 98.9 99.1 1520 1000 1700 2400 N1525
1250 6.0 2500 12,500 98.8 98.9 99.1 1700 1000 1780 3000 N1526
1600 6.0 2800 14,000 98.9 99.1 99.2 1750 1000 1820 3400 N1527
2000 6.0 3700 16,500 99.0 99.1 99.2 1805 1200 2040 4200 N1528
2500 6.5 4300 21,000 99.0 99.1 99.2 1985 1200 2150 5000 N1529
3150 7.0 6200 22,000 99.1 99.2 99.2 2220 1205 2190 6250 N1530
Note:
Other sizes and voltages up to 33kV are available on request. Lead times need to be confirmed at the time the order is placed.

DISTRIBUTION TRANSFORMERS

Rated Power No-Load Loss Load Loss Impedance Physical Attributes Product Code
Length Width Height Oil Volume Total Mass
(KVA) (W) (%) (mm) (mm) (mm) (Litres) (kg) Inland Coastal
SINGLE PHASE
11 000 / 240 Volts
16 80 400 4,5 765 632 624 48 130 N1531 N368
25 110 530 4,5 765 632 764 56 176 N6099 N6100
32 130 630 4 655 980 865 79 220 N376 N171
22 000 / 240 Volts
16 100 400 4,5 765 632 739 48 157 N370 N165
25 140 530 4,5 765 632 799 56 192 N6101 N6102
32 170 630 4 655 1055 865 90 240 N377 N172
THREE PHASE
6 600 / 420 Volts
25 120 570 4,5 950 730 670 100 280 N6103 N6104
50 180 1000 4,5 1000 750 770 150 470 N6105 N6106
100 300 1700 4,5 1253 1000 850 196 535 N779 N6107
200 520 2700 4,5 1587 1100 910 290 1070 N780 N6108
315 720 3800 4,5 1689 1268 900 320 1280 N781 N6109
500 1100 5400 5,0 1844 1618 900 495 1700 N6110 N6111
11 000 / 420 Volts
25 120 570 3,6 950 730 670 113 300 N372 N169
50 180 1000 4,5 1000 750 770 153 495 N1532 N1533
100 300 1700 4,5 1253 1000 850 196 535 N1534 N163
200 520 2700 4,5 1587 1100 818 290 1070 N1535 N167
315 720 3800 4,5 1689 1268 900 380 1290 N1536 N373
500 1100 5400 5,0 1844 1618 900 495 1771 N391 N6112
22 000 / 420 Volts
25 150 570 3,6 950 730 670 98 300 N1537 N1538
50 220 1000 3,5 1000 800 770 159 450 N398 N1539
100 360 1700 4,5 1253 1000 850 119 535 N1540 N226
200 600 2700 4,5 1587 1100 818 296 1150 N1541 N227
315 840 3800 4,5 1689 1268 882 570 1565 N374 N1542
500 1180 5400 5,0 2004 1615 900 495 2088 N383 N6113
33 000 / 420 Volts
25 170 570 4,5 1000 1100 1050 160 370 N456 N6114
50 250 1000 4,5 1036 1183 1081 248 546 N457 N6115
100 400 1700 4,5 1263 1430 1101 351 915 N458 N6116
200 650 2700 4,5 1554 1482 1226 486 1310 N459 N6117
315 890 3800 4,5 1850 1300 1400 390 1500 N466 N6118
Note:
  • Other additional types, sizes, voltages, vector groups and impedences are also available as well as cast resin (dry type) and miniature substations.
  • Available in base or pole mounted.
  • Detailed required specifications to be submitted with your enquiry.
  • Lead times need to be confirmed at the time the order is placed.
  • Physical attributes may change.
  • We sell SABS 780/ESKOM specification DISSCAAH4 DYN11 distribution class transformers in the following ratings: 16-500kVA/6600-33 000V.