Description
Total Energy Capacity [kWh]: 80
Energy, 90% DoD [kWh]: 72
Energy, 80% DoD [kWh]: 64
Nominal Voltage [V]: 410
Max/Min Operating Voltage [V]: 454/365
Max/Cont Discharge Current [A]: 250/200
Max/Cont Discharge Power [kW]: 102/80
Max and Cont Charge Current [A]: 200
Weight [kg]: 637
Dimensions on or against wall, excluding protuberances such as glands and breaker- handle Height x Width x Depth [mm]: 1451x 668×566
DC Connection: Fly Leads [no. per electrode]: 1 x 50mm
External Interfacing: CAN Bus
Enclosure: an aluminum enclosure painted white, for use indoors or fully protected under-cover environments, rated to IP20
Protection: Shunt Trip Circuit Breaker sized to suit max current, can be tripped by BMS if critical fault include overcurrent, cell under and over voltage, temperature, weak cell detection, minimum SOC control, and manual reset
Human Interface: State of Charge Display (0 to 100%), Error light, Error Reset Button, USB Plug for Programming
Service Life: 10 year (or 4000 cycles) warranty for 80% average DoD, 13–15 years (>5 500 cycles) expected life at 70% DoD, 15-20 years at 50% DoD (>7 000 cycles)