House Wire

600/1000V

Cable Description

High conductivity annealed stranded copper conductors to SANS 1411 Part 1. Insulated with PVC and skin coloured in plain colours to SANS 1411 Part 2. Cable is manufactured to SANS 1507 Part 2.

Installation Information

For the wiring of industrial buildings, housing, control panels and light fittings.

Properties
  • Specifications : SANS 1507-2
  • Temperature Range : -10°C to 70°C
  • Voltage Rating : 600/1000V
  • Core Identification : Complete range of colours
  • Packaging : 100mt shrink-wrapped perforated coils/500mt reels
  • Technical Data

    Cable SizeNominal Stranding Number x DiameterApproximate Cable DiameterCurrent Rating*Conductor Resistance @ 20ºC Maximum1OI Voltage DropApproximate Cable Mass
    (mm2)(mm)(A)(Ω/km)(mV/A/mt)(kg/100mt)
    600/1000 V
    17/0,423.01718.1431.7
    1.57/0,533.32112.1292.2
    2.57/0,66**3.6277.41183.2
    47/0,86**4.5364.61115.2
    67/1,04**5.0453.087.47.0
    107/1,35**6.0611.834.411.1
    167/1,67**6.9781.152.816.7
    2519/1,38**8.41040.731.725.6
    3519/1,62**9.51250.521.334.7
    5019/1,88**11.31490.390.9347.2
    7019/2,28**12.61900.270.6566.1
    9519/2,5015.82380.190.4897.6
    12037/2,0317.52720.150.38120.0
    15037/2,2819.73080.120.32147.0
    18537/2,5022.03500.100.26182.2

    Product Code

    Cable SizeBlackBlueBrownGreen/ YellowGreyOrangePinkVioletRedWhiteYellow
    (mm2)
    1F0000232F0000233F0000234F0000235F0000236F0000237F0000238F0000239F0000240F0000241F0000242
    1.5F0000245F0000246F0000247F0000249F0000250F0000252F0000253F0000254F0000256F0000258F0000259
    2.5F0000262F0000263F0000264F0000266F0000267F0000268F0000269F0000270F0000272F0000274F0000275
    4F0000278F0000279F0000280F0000282F0001305F0000283F0000284F0000285F0000287F0000289F0000290
    6F0000293F0000294-F0000296----F0000298F0000300-
    10F0000303F0000304-F0000306----F0000308F0000310-
    16F0000313F0000314-F0000316----F0000318F0000320F0000321
    25F0000323F0000324-F0000326----F0000327F0000328-
    35F0000330F0000331-F0000333----F0000335F0000337-
    50F0000340F0000341-F0000343----F0000344F0000346-
    70F0000349F0002343-F0000352----F0000354F0000355-
    95F0000356F0001315-F0000358----F0002346F0001316-
    120F0000360--F0000361----F0001317--
    150F0001320--F0002351----F0000363--
    185F0000364--F0000365-------
    * Note
  • Rating calculated for 1kV cable.
  • Rating based on two touching cables installed in a duct.
  • Assumed ambient air temperature is 30°C.
  • Assumed maximum conductor temperature is 70°C.
  • ** Note
  • Compacted Conductors.
  • Note
  • Items above with (-) in the Product Code column are available on special request.